A 300 lx target on a lighting schedule means 300 lux maintained on the working plane after dirt, ageing and lamp depreciation — not 300 lux on the day the ceiling was commissioned. That gap is usually a factor of 0.8, and it is the reason a room that measures 300 lx in a fresh install measures 240 lx two years later. This reference gives the lux levels that EN 12464-1 and common practice ask for by space, the maintenance factor arithmetic that connects design values to delivered values, and the measurement method that stops a site reading from being argued about for a week.
1. What lux means in practice
Lux is luminous flux per unit area: 1 lx = 1 lm/m². It is a property of the surface, not the fixture. Move the same fitting from a 2.4 m ceiling to a 3.6 m ceiling and the floor lux drops by more than half, because illuminance follows the inverse square of distance.
Two clarifications save most site arguments. First, lux is measured on a plane, and horizontal floor lux is not vertical wall lux. A wall washer can put 200 lx on a wall and 40 lx on the floor two metres away.
Second, lux says nothing about comfort. A room at 100 lx with a shielded source feels better than one at 150 lx with a bare LED at eye level.
Room surfaces finish the job. A white ceiling returns 70–80% of the light that hits it, a mid-grey wall 40–50%, a dark timber floor 10–20%. That is why the same fitting specification produces 300 lx in one lobby and 180 lx in the next, and why a reflectance survey is worth an hour on a refurbishment where finishes are changing.
The numbers that follow are maintained values, which is the convention in EN 12464-1. To convert to the initial value a contractor must install, divide by the maintenance factor — 300 lx maintained at MF 0.8 means 375 lx initial. Contractors who work in initial values and clients who check in maintained values will disagree forever unless someone writes the factor down.
2. Hotel lux table by area
Hotels sit between two standards. EN 12464-1 sets the task minimums; guest expectation sets the ambience. A lobby at exactly 200 lx reads as functional rather than hospitable, so most operators run the ambient layer at 150–200 lx and add accent layers that put 500–1,000 lx on reception desks, art and floral displays.
| Area | Maintained lux | Notes |
|---|---|---|
| Reception desk | 300 lx | Vertical 200 lx on the guest’s face for recognition |
| Lobby ambient | 200 lx | 4–6 m ceilings; 15–25 W downlights, 1,500–2,500 lm each |
| Corridor, lift lobby | 100 lx | Night mode 30–50 lx is common and not a defect |
| Guestroom ambient | 50–100 lx | Measured at 0.75 m; warm 2700–3000 K |
| Guestroom reading | 300 lx | At the pillow, on the page, not at the ceiling |
| Guestroom desk | 500 lx | Task light preferred over a ceiling layer |
| Bathroom mirror | 300 lx | Vertical, at face height; 4000 K acceptable here |
| Restaurant, dining | 200 lx | Table top 200–300 lx; the room can sit at 100 lx |
| Bar counter | 150–200 lx | Back bar 300 lx if bottles must read |
| Meeting room | 500 lx | Vertical 300 lx for video calls |
| Ballroom, pre-function | 200 lx | Design for 500 lx on demand, not continuously |
| Back of house, kitchen | 500 lx | 3500–4000 K, Ra ≥ 80 |
Corridors are where most projects overshoot. A 2.4 m wide corridor at 200 lx costs about twice the energy of one at 100 lx and reads as clinical. The correction is usually to drop the general layer and add a low-level night circuit at 10–20% output.
3. Residential lux table
Domestic lighting is judged by task, not by code. The values below are working targets that hold up in a room-by-room review and are consistent with EN 12464-1 where the standard has an opinion.
| Room | Ambient | Task | Colour temperature |
|---|---|---|---|
| Living room | 100–150 lx | 300 lx reading corner | 2700 K |
| Dining | 100–150 lx | 200 lx on the table | 2700 K |
| Kitchen | 150–200 lx | 300–500 lx worktop | 3000–4000 K |
| Bedroom | 50–100 lx | 300 lx reading at the head | 2700 K |
| Bathroom | 100 lx | 300 lx at the mirror | 3000–4000 K |
| Home office | 150–200 lx | 500 lx on the desk | 3000–4000 K |
| Stairs, hallway | 100 lx | — | 2700 K |
Colour temperature shifts the effective brightness. A 2700 K scheme reads slightly dimmer than 3000 K at the same measured lux — roughly a 1.05× difference in perceived flux — so budget 5–10% more illuminance when the brief specifies 2700 K. It is a small correction that decides whether a living room feels warm or simply dim.
Two rules of thumb make these numbers usable. A bedroom at 50 lx ambient with a 300 lx reading light needs separate circuits, otherwise the reading light becomes the room light. And a kitchen at 500 lx over the whole floor is unpleasant at night; put the 500 lx under the wall units and keep the ambient layer at 150 lx.
4. Measuring lux correctly
A €150 lux meter is accurate enough for commissioning if it is cosine-corrected and recently calibrated. The errors come from method, not hardware.

- Measure the plane you named. Floor lux at 0 m is not task lux at 0.75 m; the difference at 2.7 m mounting height is roughly 30%.
- Keep your body out of the light path. A person standing between a 24° downlight and the meter can halve the reading.
- Measure at night or black out the windows. 200 lx of daylight through a sheer curtain will mask a badly lit room entirely.
- Use a grid, not a spot. EN 12464-1 sizes the grid by room dimension: spacing ≤ 0.2 × 5^(log₁₀ d). For a 5 m room that is 0.62 m; for 10 m it is 1.0 m.
- Record minimum, average and uniformity (minimum ÷ average). A room at 300 lx average with 90 lx minimum will be complained about.
- Note the dimmer position and the scene. A reading taken at 100% is not evidence about the 30% scene the hotel actually runs at dinner.
Log the readings against the drawing, not in a notebook. A one-page table per room type — grid point, measured lux, dimmer scene, date — turns a dispute into a comparison, and it is the document a facilities team will still be using in five years when the fittings are reordered.
If the measured value is below the schedule, the usual order of causes is: wrong beam angle installed, driver output current set lower than specified, dirty diffuser, or a dimmer trimming below full output. Check the driver current first — it takes five minutes and explains about a third of the shortfalls we see.
5. Maintenance factor and dirt depreciation
Maintenance factor (MF) is the multiplier that connects the clean, new installation to the value you are entitled to have after two or three years. EN 12464-1 expects design values to be maintained values, so the installed initial lux must be higher.

MF is built from three parts: lamp lumen maintenance (LLMF), luminaire maintenance from dirt on optics and diffusers (LMF), and room surface maintenance (RSMF). A realistic hotel figure:
- LLMF 0.90 — LED at L80B10 over the design life, well within a 50,000 h rating.
- LMF 0.90 — sealed IP44 downlights in a clean lobby, cleaned annually.
- RSMF 0.98 — light-coloured walls and ceilings, cleaned on the same cycle.
- MF = 0.90 × 0.90 × 0.98 = 0.79, rounded to 0.8.
Use 0.8 for a clean interior with accessible fixtures and annual cleaning. Drop to 0.7 for kitchens, atria, or any space where the fittings cannot be reached without scaffolding. Go to 0.65 for a coastal or dusty environment with open optics. Each 0.05 of MF is roughly 6% more installed lumens, and pretending the factor is 1.0 is the most common way a project ends up 20% dark.
The factor also decides the cleaning interval. If the operating budget only supports cleaning every three years, use the three-year LMF, not the one-year figure. That is a maintenance decision being made in the lighting design, and it belongs in the O&M manual rather than in a verbal agreement.
6. Why lumen output is not lux
A luminaire’s lumen figure is the total flux leaving the optics. Lux is what survives the trip to the surface: distance, beam angle, room reflectance and maintenance all take a cut. A 3,000 lm downlight in a 12 m² bathroom and the same fitting in a 40 m² lobby produce completely different floor lux, and neither number is on the box.
The conversion is E = I / d² for on-axis illuminance, where I is candela. A 1,500 lm 36° fitting spreads over a 1.95 m circle at 3 m — 2.99 m² — so 500 lx average is the theoretical ceiling before any loss. Two fittings with the same lumens and different beam angles have different candela, and therefore different lux at the same height. That is why specifiers who compare lumen-per-watt across a schedule are comparing efficiency, not lighting.
For a first-pass estimate, use the lumen method: average lux = (fixtures × lumens × utilisation factor × MF) ÷ floor area. Utilisation factor runs 0.5–0.7 in a normal room with light surfaces and drops to 0.3 in a dark, tall space. If the estimate and the photometric calculation disagree by more than 20%, the utilisation factor is usually the culprit.
Power density is the cross-check that catches a design drifting. Hotel guestrooms run 6–9 W/m², offices 8–11 W/m², retail 15–25 W/m². If a guestroom scheme lands at 14 W/m², either the lux target is wrong or the optics are too wide for the ceiling height; adding more wattage will not fix either.
One practical consequence: when a client asks for “brighter”, the answer is often a wider beam angle or a second layer, not more lumens. Adding output to a 24° fitting raises the centre of the pool and the glare, while the corners of the room stay dark. See how beam angle, lux and glare interact before changing wattage.
Hotel projects also need the numbers to survive a night audit: 100 lx in a corridor at 03:00 is not the same specification as 100 lx at 19:00. Scene-based commissioning, with lux targets recorded per scene, is the only way to keep both. Hospitality schemes that get this right are usually the ones where the lighting concept was built around layers rather than a single figure.
Frequently asked questions
What are typical lux levels for a hotel corridor?
100 lx maintained at floor level, with a night scene at 30–50 lx. Uniformity should stay above 0.4 so the corridor does not read as a series of pools. Guestroom doors benefit from a vertical 50 lx so a key card can be found without a phone torch.
Is 300 lx enough for reading?
300 lx at the page is the usual minimum for sustained reading, and it is what EN 12464-1 implies for a guestroom reading position. Below 200 lx most adults start holding the book closer. The light must also be positioned so the page is lit without the source in the reader’s eye line.
How do I convert lux to lumens?
You cannot do it directly. Lux times area gives lumens arriving on that surface, so 300 lx over 10 m² is 3,000 lm delivered. To get from a fixture’s lumen rating to lux you also need beam angle, mounting height and a utilisation factor, or a photometric calculation.
Why does my lux meter read lower than the design?
Check the maintenance factor first: a 300 lx design at MF 0.8 requires 375 lx when new. Then check driver output current, dimmer position, beam angle actually installed, and whether you measured at the task plane or the floor. Daylight contamination makes readings higher, not lower.
Next step
Lux targets are only useful once they are attached to a layout. Qilux prepares room-by-room lux calculations, maintained-value tables and layouts for hotel and residential projects, with the maintenance factor stated on the drawing so commissioning has something to check against. Send the floor plans and room types through our engineering capabilities page and the schedule comes back per room.