Emergency lighting is a compliance product, not a design product, and it is usually specified late. That ordering is backwards: the escape route, the exit signs and the duration requirement shape the ceiling layout, and retrofitting them into a finished lobby is expensive.

What the regulations require

EN 1838 sets the numbers. Escape routes need a minimum of 1 lux along the centre line at floor level, with a uniformity ratio of 1:40. Open areas larger than 60 square metres need 0.5 lux. High-risk task areas need 10 percent of the normal illuminance, and the whole system must run for at least three hours after a mains failure. Exit signs follow the same duration and must be visible from any point in the escape route.

Maintained and non-maintained

A maintained fitting is lit continuously and doubles as normal lighting, which suits cinemas, bars and corridors where the general lighting is dimmed or switched off. A non-maintained fitting stays dark until the supply fails, which suits offices and back of house. The choice is made by the fire strategy, not by the lighting designer.

Self-contained or central battery

Self-contained fittings carry their own battery and test circuit. They are cheaper to install, easier to retrofit and fail one at a time. Central battery systems move the battery and the testing to a plant room, which reduces the number of items to maintain in a public area but raises the cost of the cabling and the consequence of a single failure. For a hotel refurbishment, self-contained is usually the pragmatic answer.

Testing and monitoring

Monthly function tests and an annual full-duration test are a legal requirement, and the log is inspected. Addressable DALI-2 emergency drivers report their own status to the building management system, which converts a clipboard task into an exception report. On a 200-room property that difference is measured in maintenance hours per month.

How emergency lighting is quoted here

Emergency luminaires are specified per project rather than stocked, because the exit sign legend, the mounting and the monitoring protocol are all project-specific. Send the escape route drawings and the fire strategy, and we return a schedule with durations, legends and the test regime written into the quotation. The fixtures themselves are sourced to match the finish of the general lighting so that the ceiling does not read as two systems.