0-10V dimming is the oldest analog interface still in daily use, and it survives because it is boring. Two wires carry a DC voltage, 10 V means full output, 1 V means 10%, and below about 0.5 V the driver switches off. There is no addressing, no software and no commissioning tool, which is why an electrician can terminate it correctly on the first visit. The limits are just as simple: every fixture on the pair does the same thing, the bottom of the range is usually 10%, and a controller that cannot supply enough current will dim some fixtures and not others. This page covers the signalling, the sink-versus-source trap, the wiring rules that decide whether it works on a 60 m run, and where 0-10V still beats DALI on installed cost.

1. How 0-10V signalling works

The controller produces a DC control voltage between 0 and 10 V. The driver has a high-impedance input that reads that voltage and maps it onto output current. Ten volts is 100%, one volt is 10%, and the mapping in between is set by the driver’s curve — square law for most architectural products, linear on some older ones.

The important point is that the signal carries almost no power. The controller sources a small current, typically 10 mA, and each driver sinks 0.5–2 mA to hold the voltage it needs. The pair is a current-limited loop, not a power circuit, which is why 0.5–1.5 mm² signal cable is enough.

Below the bottom of the range, behaviour differs by driver. Some switch off at 0.5 V, some at 1 V, and some hold their minimum output until the signal reaches zero. That is the practical difference between 0-10 V and the older 1-10 V scheme: on a 1-10 V system, 1 V is the floor and 0 V is off, while a 0-10 V driver may treat 0 V as off as well. Mixing the two on one controller produces either a fixture that never reaches minimum or one that never turns off, and it is a common retrofit fault.

The interface is SELV and normally wired as a Class 2 circuit, so it can run in the same containment as mains cable only if the cable insulation and segregation rules allow it. Most projects use a separate signal cable or a composite cable with a screened pair, which costs more per metre and removes a whole class of noise problems.

2. Sink vs source: the compatibility trap

There are two ways to build a 0-10 V port, and they are not interchangeable.

Functional diagram illustrating source and sink compatibility between a dimming controller and LED driver

A sink driver is the common one: the controller supplies the 10 V and the driver draws current from it. A source driver produces the 10 V itself and expects the controller to sink current. Put a source driver on a sink controller and nothing happens, or the voltage sits at the wrong level and the fixture flickers at one fixed brightness. Put a sink driver on a source controller and the same thing happens in reverse.

Two checks settle it before an order is placed. Ask for the driver’s input type in writing, and count the load. A controller rated 10 mA with drivers sinking 1 mA each is good for ten fixtures; at 2 mA each it is good for five. Exceeding that does not fail cleanly — the voltage sags progressively, so the first fixtures in the run dim further than the last ones, and someone blames the cable.

Sink driverSource driver
Who supplies the 10 VController드라이버
Current per driver0.5–2 mA drawnUp to 10 mA supplied
Works withControllers with a 10 V source outputControllers with a sink input
Fixtures per 10 mA channel5–10 depending on the driverLimited by controller sink rating
Typical failureVoltage sag on long runsNo dimming at all

Many controllers offer both modes on one terminal, selected by a jumper. That is also where the second fault comes from: a controller left in source mode on a sink circuit looks like a dead channel, and the electrician replaces a driver that was working.

3. Wiring, polarity and voltage drop

Two wires, and on most drivers the polarity does matter even though the input is protected against reversal. Reversed polarity on a protected input usually works; reversed polarity on an unprotected one usually does not, and the failure is a driver held at full output with no dimming, which reads like a control fault rather than a wiring fault.

Voltage drop is the design calculation that nobody does. The signal is a voltage, so any drop in the cable is a dimming error: 1 V of drop is 10% of the range. Keep the total drop under 2% of 10 V, or 0.2 V, at full load. With 20 drivers sinking 1 mA each, the loop carries 20 mA; 100 m of 0.5 mm² copper is roughly 7 Ω, which gives 0.14 V, or 1.4% — inside the limit. Double the run or halve the cable and it is not, and the symptom is a zone that cannot reach 100%.

Noise is the other constraint. A 0-10 V pair running parallel to mains for 30 m will pick up induced voltage, and a driver reading 0.3 V of noise at the bottom of its range will flicker or refuse to switch off. Screened cable with the screen earthed at the controller end only, and physical separation of at least 100 mm from power cables, removes most of it.

Terminations cause more callbacks than the electronics. Most controllers take two conductors per terminal, so daisy-chaining twenty drivers through one block puts twenty conductors in one place, which is where loose strands and intermittent dimming start. Use a marshalling terminal or a small distribution block.

4. Why 0-10V usually stops at 10%

The 10% floor is not a conspiracy. It is what happens when a voltage interface is asked to resolve a range that spans two orders of magnitude.

Map the range linearly and 1 V corresponds to 10% output, 0.5 V to 5%, 0.1 V to 1%. To hold 1% reliably, the driver has to resolve 10 mV at its input in the presence of supply noise, cable drop tolerance and its own offset. That is possible with a good differential input and a stable reference, and it is not what a low-cost analog driver does. Most settle for a 1 V floor and an off state below it, which gives the 10% minimum that appears on the datasheet.

There is a second reason. At low output the control loop has less margin, and a small voltage error becomes a large relative current error: a 20 mV offset invisible at 8 V is 2% of the signal at 1 V, enough to make one fixture in a group look brighter than its neighbours. Manufacturing tolerance alone makes a 1% floor expensive on an analog interface.

Drivers that do reach 1% on 0-10 V exist. They use a logarithmic mapping, a tighter reference and often a filtered input, and they cost more. If the brief says 1%, ask for the figure at 1% with the test method, in the same way you would for flicker. A datasheet line that says “1–100%” without qualification usually means the driver accepts a 0-10 V signal and dims to 1% on DALI, not on the analog input.

5. 0-10V vs DALI: cost and function

The cost argument is real and it is usually overstated. A 0-10 V controller is cheaper per zone, needs no commissioning software and can be installed by any electrical contractor. DALI costs more per device, needs a commissioning engineer, and needs somebody to own the addressing schedule afterwards. On a small restaurant with five zones and a keypad, 0-10 V wins on both capital and operating cost.

What DALI buys is addressability. Sixty-four addresses on one line, sixteen groups and sixteen scenes mean a corridor can dim in bands, a ballroom can recall four looks, and a single fixture can be isolated for maintenance without shutting a zone. D4i adds diagnostics: hours run, energy, driver temperature, failure prediction. 0-10 V has none of that, because every fixture on the pair is doing the same thing by definition.

The decision usually comes down to three questions. Does the space need more than one scene in the same zone? Does the client want per-fixture energy data? Will someone need to change the grouping after handover without pulling cable? Two yes answers point at DALI; none point at 0-10 V.

0-10 VDALI-2 / D4i
제어 유형아날로그 전압디지털 버스
주소 지정없음, 구역 단위만 지원라인당 주소 64개, 그룹 16개, 장면 16개
일반적인 조광 범위최저 밝기 10%, 프리미엄 드라이버는 1%0.1–1%
시운전각 조명기구에서 전압 확인주소 지정, 장면 프로그래밍, 인계 파일
진단없음D4i: 작동 시간, 에너지, 온도, 고장
적합한 용도소규모 구역, 단순한 장면, 레트로핏호텔, 사무실, 장면 제어가 필요한 모든 곳

하이브리드 방식은 가능하며 유용합니다. DALI-0~10V 게이트웨이를 사용하면 기존 아날로그 구역을 DALI 장면 제어 시스템에 연결할 수 있고, DALI 모듈이 장착된 0~10V 컨트롤러를 사용하면 그 반대도 가능합니다. 두 방식 모두 유효하며 동일한 원칙을 따라야 합니다. 부하 측에는 하나의 프로토콜만 사용하고, 게이트웨이에서 변환하며, 접속함에서 두 프로토콜을 절대 혼합하지 않아야 합니다. 건물 전체에서 두 기술을 함께 사용하는 프로젝트에서는 대개 이를 상업용 조명 범위 에 문서화하여 유지보수팀이 어느 것이 어느 것인지 알 수 있도록 합니다.

6. 시운전 점검

0~10V 시스템의 시운전은 전압을 측정하는 작업이며, 조명기구 설치를 마친 뒤 구역당 약 10분이 걸립니다.

Commissioning checklist for control signal compatibility, dimming response, low-end behavior and switch-off

부하를 연결하지 않은 상태에서 컨트롤러부터 측정합니다. 100%에서 10.0V, 10%에서 1.0V, 꺼짐 상태에서 0V여야 합니다. 그런 다음 부하를 연결한 상태로 배선 구간의 마지막 조명기구에서 측정해 비교합니다. 전압 강하가 0.2V를 넘으면 케이블이나 단자 연결 문제, 또는 채널에 드라이버가 너무 많이 연결된 문제일 수 있습니다. 이어서 양 끝값을 확인합니다. 10V에서는 모든 조명기구가 최대 출력이어야 하고, 1V에서는 모두 같은 밝기여야 합니다. 어느 하나가 더 밝다면 드라이버마다 조광 곡선이 다른 것입니다. 전압을 아무리 조정해도 서로 다른 브랜드 제품을 혼용한 문제는 해결되지 않습니다.

꺼짐 상태도 제대로 확인합니다. 일부 드라이버는 0V에서도 3~5% 출력을 유지해 불이 켜진 공간에서는 알아차리기 어렵지만, 밤에는 눈에 띕니다. 어두운 공간에서 컨트롤러를 0으로 설정해 확인하세요. 그런 다음 낮은 밝기에서 깜박임이 있는지 확인합니다. 아날로그 드라이버가 1V 최저점에 가까워질 때 잡음이 있는 신호가 가장 잘 드러납니다.

인수인계 파일에 전압, 드라이버 모델, 채널별 조명기구 수를 기록합니다. 3년 차에 드라이버를 교체할 때, 이 파일이 있으면 5분 만에 교체할 수 있지만 없으면 오후 내내 원인을 추측해야 할 수도 있습니다.

확인 항목Target드러나는 고장
컨트롤러 무부하 출력 전압최대 출력에서 10.0V, 10%에서 1.0V컨트롤러 출력 고장
부하가 연결된 상태에서 마지막 조명기구의 전압전압 강하 0.2V(2%) 미만케이블, 단자 연결, 채널 과부하
1V에서 밝기 균일도모든 조명기구 간 밝기 차이 2% 이내서로 다른 드라이버 조광 곡선
0V에서 꺼짐 상태어두운 공간에서 눈에 보이는 출력이 없어야 함드라이버의 최소 출력 유지
1V에서 깜박임눈에 보이는 밝기 변동이 없고, 플리커율은 5% 미만잡음, 오프셋, 불안정한 저조도 구간

마지막으로 한 가지만 더 확인하면 현장 재방문을 막을 수 있습니다. 컨트롤러의 0V 기준이 드라이버의 기준과 일치하는지 확인하세요. 컨트롤러가 다른 배전반에서 전원을 공급받는다면 기준 전압 간에 수백 밀리볼트의 차이가 생겨 조광 곡선 전체가 이동하고, 해당 구역은 조광 범위의 양 끝에 도달하지 못합니다.

다음 단계

구역 수가 적고 장면이 단순하며, 추측이 아니라 전압을 측정할 전기 기술자가 현장에 있는 경우 0~10V 방식이 적합합니다. 프로젝트가 이에 해당한다면, 조광 가능한 드라이버의 범위와 제어 옵션을 이미 지정된 컨트롤러에 맞출 수 있으며, 다운라이트 배치 계획 주문 확정 전에 싱크 전류와 저단 동작을 확인할 수 있습니다.