{"id":12010,"date":"2026-11-22T01:00:00","date_gmt":"2026-11-22T01:00:00","guid":{"rendered":"https:\/\/qiluxlighting.com\/?p=12010"},"modified":"2026-11-16T03:31:17","modified_gmt":"2026-11-16T03:31:17","slug":"0-10v-dimming","status":"publish","type":"post","link":"https:\/\/qiluxlighting.com\/pt\/0-10v-dimming\/","title":{"rendered":"0-10V Dimming Explained for Project Lighting"},"content":{"rendered":"<p class=\"intro\">0-10V dimming is the oldest analog interface still in daily use, and it survives because it is boring. Two wires carry a DC voltage, 10 V means full output, 1 V means 10%, and below about 0.5 V the driver switches off. There is no addressing, no software and no commissioning tool, which is why an electrician can terminate it correctly on the first visit. The limits are just as simple: every fixture on the pair does the same thing, the bottom of the range is usually 10%, and a controller that cannot supply enough current will dim some fixtures and not others. This page covers the signalling, the sink-versus-source trap, the wiring rules that decide whether it works on a 60 m run, and where 0-10V still beats DALI on installed cost.<\/p>\n<h2>1. How 0-10V signalling works<\/h2>\n<p>The controller produces a DC control voltage between 0 and 10 V. The driver has a high-impedance input that reads that voltage and maps it onto output current. Ten volts is 100%, one volt is 10%, and the mapping in between is set by the driver&#8217;s curve \u2014 square law for most architectural products, linear on some older ones.<\/p>\n<p>The important point is that the signal carries almost no power. The controller sources a small current, typically 10 mA, and each driver sinks 0.5\u20132 mA to hold the voltage it needs. The pair is a current-limited loop, not a power circuit, which is why 0.5\u20131.5 mm\u00b2 signal cable is enough.<\/p>\n<p>Below the bottom of the range, behaviour differs by driver. Some switch off at 0.5 V, some at 1 V, and some hold their minimum output until the signal reaches zero. That is the practical difference between 0-10 V and the older 1-10 V scheme: on a 1-10 V system, 1 V is the floor and 0 V is off, while a 0-10 V driver may treat 0 V as off as well. Mixing the two on one controller produces either a fixture that never reaches minimum or one that never turns off, and it is a common retrofit fault.<\/p>\n<p>The interface is SELV and normally wired as a Class 2 circuit, so it can run in the same containment as mains cable only if the cable insulation and segregation rules allow it. Most projects use a separate signal cable or a composite cable with a screened pair, which costs more per metre and removes a whole class of noise problems.<\/p>\n<h2>2. Sink vs source: the compatibility trap<\/h2>\n<p>There are two ways to build a 0-10 V port, and they are not interchangeable.<\/p>\n<figure class=\"qilux-image\" data-image-id=\"D3-B01\"><a href=\"https:\/\/qiluxlighting.com\/wp-content\/uploads\/2026\/11\/qilux-d3-body-01-0-10v-dimming.webp\" target=\"_blank\" rel=\"noopener\"><img loading=\"lazy\" src=\"https:\/\/qiluxlighting.com\/wp-content\/uploads\/2026\/11\/qilux-d3-body-01-0-10v-dimming.webp\" alt=\"Functional diagram illustrating source and sink compatibility between a dimming controller and LED driver\" title=\"Check the controller and driver as a pair\" width=\"1600\" height=\"1000\" decoding=\"async\"><\/a><\/figure>\n<p>A <strong>sink<\/strong> driver is the common one: the controller supplies the 10 V and the driver draws current from it. A <strong>source<\/strong> driver produces the 10 V itself and expects the controller to sink current. Put a source driver on a sink controller and nothing happens, or the voltage sits at the wrong level and the fixture flickers at one fixed brightness. Put a sink driver on a source controller and the same thing happens in reverse.<\/p>\n<p>Two checks settle it before an order is placed. Ask for the driver&#8217;s input type in writing, and count the load. A controller rated 10 mA with drivers sinking 1 mA each is good for ten fixtures; at 2 mA each it is good for five. Exceeding that does not fail cleanly \u2014 the voltage sags progressively, so the first fixtures in the run dim further than the last ones, and someone blames the cable.<\/p>\n<table>\n<thead>\n<tr>\n<th><\/th>\n<th>Sink driver<\/th>\n<th>Source driver<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Who supplies the 10 V<\/td>\n<td>Controller<\/td>\n<td>Driver<\/td>\n<\/tr>\n<tr>\n<td>Current per driver<\/td>\n<td>0.5\u20132 mA drawn<\/td>\n<td>Up to 10 mA supplied<\/td>\n<\/tr>\n<tr>\n<td>Works with<\/td>\n<td>Controllers with a 10 V source output<\/td>\n<td>Controllers with a sink input<\/td>\n<\/tr>\n<tr>\n<td>Fixtures per 10 mA channel<\/td>\n<td>5\u201310 depending on the driver<\/td>\n<td>Limited by controller sink rating<\/td>\n<\/tr>\n<tr>\n<td>Falha t\u00edpica<\/td>\n<td>Voltage sag on long runs<\/td>\n<td>No dimming at all<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Many controllers offer both modes on one terminal, selected by a jumper. That is also where the second fault comes from: a controller left in source mode on a sink circuit looks like a dead channel, and the electrician replaces a driver that was working.<\/p>\n<h2>3. Wiring, polarity and voltage drop<\/h2>\n<p>Two wires, and on most drivers the polarity does matter even though the input is protected against reversal. Reversed polarity on a protected input usually works; reversed polarity on an unprotected one usually does not, and the failure is a driver held at full output with no dimming, which reads like a control fault rather than a wiring fault.<\/p>\n<p>Voltage drop is the design calculation that nobody does. The signal is a voltage, so any drop in the cable is a dimming error: <strong>1 V of drop is 10% of the range<\/strong>. Keep the total drop under 2% of 10 V, or 0.2 V, at full load. With 20 drivers sinking 1 mA each, the loop carries 20 mA; 100 m of 0.5 mm\u00b2 copper is roughly 7 \u03a9, which gives 0.14 V, or 1.4% \u2014 inside the limit. Double the run or halve the cable and it is not, and the symptom is a zone that cannot reach 100%.<\/p>\n<p>Noise is the other constraint. A 0-10 V pair running parallel to mains for 30 m will pick up induced voltage, and a driver reading 0.3 V of noise at the bottom of its range will flicker or refuse to switch off. Screened cable with the screen earthed at the controller end only, and physical separation of at least 100 mm from power cables, removes most of it.<\/p>\n<p>Terminations cause more callbacks than the electronics. Most controllers take two conductors per terminal, so daisy-chaining twenty drivers through one block puts twenty conductors in one place, which is where loose strands and intermittent dimming start. Use a marshalling terminal or a small distribution block.<\/p>\n<h2>4. Why 0-10V usually stops at 10%<\/h2>\n<p>The 10% floor is not a conspiracy. It is what happens when a voltage interface is asked to resolve a range that spans two orders of magnitude.<\/p>\n<p>Map the range linearly and 1 V corresponds to 10% output, 0.5 V to 5%, 0.1 V to 1%. To hold 1% reliably, the driver has to resolve 10 mV at its input in the presence of supply noise, cable drop tolerance and its own offset. That is possible with a good differential input and a stable reference, and it is not what a low-cost analog driver does. Most settle for a 1 V floor and an off state below it, which gives the 10% minimum that appears on the datasheet.<\/p>\n<p>There is a second reason. At low output the control loop has less margin, and a small voltage error becomes a large relative current error: a 20 mV offset invisible at 8 V is 2% of the signal at 1 V, enough to make one fixture in a group look brighter than its neighbours. Manufacturing tolerance alone makes a 1% floor expensive on an analog interface.<\/p>\n<p>Drivers that do reach 1% on 0-10 V exist. They use a logarithmic mapping, a tighter reference and often a filtered input, and they cost more. If the brief says 1%, ask for the figure at 1% with the test method, in the same way you would for flicker. A datasheet line that says &#8220;1\u2013100%&#8221; without qualification usually means the driver accepts a 0-10 V signal and dims to 1% on DALI, not on the analog input.<\/p>\n<h2>5. 0-10V vs DALI: cost and function<\/h2>\n<p>The cost argument is real and it is usually overstated. A 0-10 V controller is cheaper per zone, needs no commissioning software and can be installed by any electrical contractor. DALI costs more per device, needs a commissioning engineer, and needs somebody to own the addressing schedule afterwards. On a small <a href=\"\/pt\/solutions\/fnb\/\">restaurant<\/a> with five zones and a keypad, 0-10 V wins on both capital and operating cost.<\/p>\n<p>What DALI buys is addressability. Sixty-four addresses on one line, sixteen groups and sixteen scenes mean a corridor can dim in bands, a ballroom can recall four looks, and a single fixture can be isolated for maintenance without shutting a zone. D4i adds diagnostics: hours run, energy, driver temperature, failure prediction. 0-10 V has none of that, because every fixture on the pair is doing the same thing by definition.<\/p>\n<p>The decision usually comes down to three questions. Does the space need more than one scene in the same zone? Does the client want per-fixture energy data? Will someone need to change the grouping after handover without pulling cable? Two yes answers point at DALI; none point at 0-10 V.<\/p>\n<table>\n<thead>\n<tr>\n<th><\/th>\n<th>0-10 V<\/th>\n<th>DALI-2 \/ D4i<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Control type<\/td>\n<td>Analog voltage<\/td>\n<td>Digital bus<\/td>\n<\/tr>\n<tr>\n<td>Addressing<\/td>\n<td>None, zone-level only<\/td>\n<td>64 addresses per line, 16 groups, 16 scenes<\/td>\n<\/tr>\n<tr>\n<td>Profundidade t\u00edpica<\/td>\n<td>10% floor, 1% on premium drivers<\/td>\n<td>0.1\u20131%<\/td>\n<\/tr>\n<tr>\n<td>Commissioning<\/td>\n<td>Voltage check at each fixture<\/td>\n<td>Addressing, scene programming, handover file<\/td>\n<\/tr>\n<tr>\n<td>Diagnostics<\/td>\n<td>Nenhuma<\/td>\n<td>D4i: hours, energy, temperature, faults<\/td>\n<\/tr>\n<tr>\n<td>Mais indicado para<\/td>\n<td>Small zones, simple scenes, retrofit<\/td>\n<td>Hotels, offices, anything with scene control<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Hybrid schemes exist and are useful: a DALI-to-0-10 V gateway lets an existing analog zone join a DALI scene engine, and a 0-10 V controller with a DALI module does the reverse. Both are legitimate, and both need the same discipline \u2014 one protocol at the load side, translated at the gateway, never mixed at a junction box. Projects that run both technologies across a building usually document them in the <a href=\"\/pt\/commercial-project-lighting\/\">commercial lighting scope<\/a> so the maintenance team knows which is which.<\/p>\n<h2>6. Commissioning checks<\/h2>\n<p>Commissioning a 0-10 V system is a voltage measurement exercise, and it takes about ten minutes per zone once the fixtures are up.<\/p>\n<figure class=\"qilux-image\" data-image-id=\"D3-B02\"><a href=\"https:\/\/qiluxlighting.com\/wp-content\/uploads\/2026\/11\/qilux-d3-body-02-0-10v-dimming.webp\" target=\"_blank\" rel=\"noopener\"><img loading=\"lazy\" src=\"https:\/\/qiluxlighting.com\/wp-content\/uploads\/2026\/11\/qilux-d3-body-02-0-10v-dimming.webp\" alt=\"Commissioning checklist for control signal compatibility, dimming response, low-end behavior and switch-off\" title=\"Confirm actual 0\u201310 V behavior\" width=\"1600\" height=\"1000\" decoding=\"async\"><\/a><\/figure>\n<p>Start at the controller with no load: 10.0 V at 100%, 1.0 V at 10%, 0 V at off. Then measure at the last fixture on the run with the load connected and compare. A drop above 0.2 V points at cable, terminations or too many drivers on the channel. Then walk the extremes: at 10 V every fixture should be at full output, and at 1 V they should all be at the same level. If one is brighter, the drivers have different curves, and no amount of voltage tweaking will fix a mix of brands.<\/p>\n<p>Check the off state properly. Some drivers hold 3\u20135% at 0 V rather than switching off, which is invisible in a lit room and obvious at night. Check it in a dark space with the controller at zero. Then check the low end for flicker: an analog driver near its 1 V floor is exactly where a noisy signal shows up.<\/p>\n<p>Record the voltages, the driver model and the number of fixtures per channel in the handover file. When a driver is replaced in year three, that file is the difference between a five-minute swap and an afternoon of guessing.<\/p>\n<table>\n<thead>\n<tr>\n<th>Verifica\u00e7\u00e3o<\/th>\n<th>Target<\/th>\n<th>Fault it reveals<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Controller open-circuit voltage<\/td>\n<td>10.0 V at full, 1.0 V at 10%<\/td>\n<td>Controller output fault<\/td>\n<\/tr>\n<tr>\n<td>Voltage at last fixture under load<\/td>\n<td>Drop &lt; 0.2 V (2%)<\/td>\n<td>Cable, terminations, overloaded channel<\/td>\n<\/tr>\n<tr>\n<td>Uniform level at 1 V<\/td>\n<td>All fixtures within 2% of each other<\/td>\n<td>Mixed driver curves<\/td>\n<\/tr>\n<tr>\n<td>Off state at 0 V<\/td>\n<td>No visible output in a dark room<\/td>\n<td>Driver holding minimum output<\/td>\n<\/tr>\n<tr>\n<td>Flicker at 1 V<\/td>\n<td>No visible modulation, percent flicker &lt; 5%<\/td>\n<td>Noise, offset, unstable low end<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>One last check saves a callout: confirm the controller&#8217;s 0 V reference matches the driver&#8217;s. If the controller is fed from a different distribution board, a few hundred millivolts between the references shifts the whole dimming curve, and the zone never reaches either end of its range.<\/p>\n<h2>Pr\u00f3ximo passo<\/h2>\n<p>0-10 V is a good answer when the zone count is low, the scenes are simple and the site has an electrician who will measure voltages rather than guess. If that describes your project, the <a href=\"\/pt\/capabilities\/\">dimmable driver range and control options<\/a> can be matched to the controller already specified, and the <a href=\"\/pt\/categoria-produto\/downlights\/\">plano de downlights<\/a> checked for sink current and low-end behaviour before the order is confirmed.<\/p>","protected":false},"excerpt":{"rendered":"<p>0-10V dimming is the oldest analog interface still in daily use, and it survives because it is boring. Two wires carry a DC voltage, 10 V means full output, 1 V means 10%, and below about 0.5 V the driver switches off. There is no addressing, no software and no commissioning tool, which is why [&hellip;]<\/p>\n","protected":false},"author":2,"featured_media":12157,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"inline_featured_image":false,"footnotes":""},"categories":[178],"tags":[],"class_list":["post-12010","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-technical-knowledge-installation"],"_links":{"self":[{"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/posts\/12010","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/users\/2"}],"replies":[{"embeddable":true,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/comments?post=12010"}],"version-history":[{"count":2,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/posts\/12010\/revisions"}],"predecessor-version":[{"id":12240,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/posts\/12010\/revisions\/12240"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/media\/12157"}],"wp:attachment":[{"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/media?parent=12010"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/categories?post=12010"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/qiluxlighting.com\/pt\/wp-json\/wp\/v2\/tags?post=12010"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}